Proceedings of the 10th Convention of the European Acoustics Association Forum Acusticum 2023 Politecnico di Torino Torino, Italy September 11 - 15, 2023 |
|
Abstract In Denmark - and probably most countries in Europe - regulatory noise limits apply for noise from ventilation systems in housing. However, during the last few decades, mechanical ventilation with heat recovery (MVHR) has become increasingly prevalent in new and retrofitted housing in Europe, and such systems may operate continuously 24 hours/day and transmit noise into and between rooms. In practice, many people get annoyed or disturbed by the noise during night or when having quiet activities. Many people complain, and some people change the operation or even destroy the system. In Denmark, the ventilation noise must comply with LAeq ≤ 30 dB for new-build and new systems in renovated housing, using a simplified version of ISO 10052. Due to dissatisfaction from occupants, it is considered reducing the limit to LAeq ≤ 25 dB in living and sleeping rooms, which is currently tested in a voluntary sustainability class (in Danish abbreviated FBK), including use of ISO 16032. The paper describes results from a case study comparing the methods, and other challenges when measuring such low noise levels are discussed, aiming at providing input for a revised field test method to be applied in the Danish regulations. |
||||||||||||||||||||