Proceedings of the 11th Convention of the European Acoustics Association Forum Acusticum / EuroNoise 2025 Málaga, Spain June 23 - 26, 2025 |
|
Abstract Windows are essential façade components that balance multiple functions, including daylighting, natural ventilation, and thermal regulation. However, conventional windows often suffer from significant energy losses and inadequate air exchange, even with regular ventilation. To address these challenges, the iclimabuilt project has developed a smart ventilated window that integrates advanced technologies such as PCM (phase-change material) heat storage, triple glazing with air-filled chambers for thermal insulation, and 3D-printed components for noise reduction and air purification. These innovations minimise energy losses, enhance thermal management, and promote occupant health and well-being. This study focuses on evaluating the acoustic performance of the three operational modes of the fans integrated into the window of a Living Lab environment. Noise measurements have been conducted following EN ISO 16032:24, with and without an acoustic filter installed in the PCM box and air filtration unit. Data were collected from three microphone positions: a corner and two reverberant field points. The analysis reveals that noise levels generated by the fans are in the 35 – 45 dB range, above standard limits. Moreover, the findings highlight the need to further optimise noise control strategies in smart windows design while maintaining their energy efficiency and indoor air quality benefits. |
||||||||||||||||||||