Proceedings of the 11th Convention of the
European Acoustics Association
Forum Acusticum / EuroNoise 2025


Málaga, Spain
June 23 - 26, 2025





Session: A03.12 Ventilation noise in dwellings: challenges, measurements, and solutions
Date: Tuesday 24 June 2025
Time: 10:20
Title: A Silencer Design for a Mechanical Heat Recovery Unit
Author(s): Darragh Mullally
John Kennedy
Pages: 841-844
DOI: https://www.doi.org/10.61782/fa.2025.0771
PDF: https://dael.euracoustics.org/confs/fa2025/data/articles/000771.pdf
Conference proceedings
Abstract

Modern homes require energy efficient airtight designs using controlled ventilation systems to retain the heat energy. Mechanical Ventilation Heat Recovery (MVHR) units help to maintain air circulation between the building and the outdoors, while not compromising energy efficiency. A significant challenge to implementation and continuous use of these devices is the noise emission. Noise from MVHRs can cause indoor noise levels to exceed the recommended levels, with respect to the Noise Rating (NR) guidelines. The noise has a frequency content below 500 Hz, which many conventional sound absorbers struggle to attenuate without large space requirements. This research develops a compact silencer suitable for a domestic MVHR unit with a large duct diameter. The design consists of stacked Helmholtz resonators with embedded necks and relatively large cavity volumes. The proposed design achieved >8dB transmission loss for frequencies 250 Hz, 300 Hz and 350 Hz. These were compared with data from an MVHR and the NR guideline and was found to reduce the MVHR SPL to below NR35 for the octave bands 250 Hz and 500 Hz.