Abstract Recent heat pump fans are nowadays often optimized towards a very low self-noise level. Still less effort is expended in the field of additional noise sources generated by spatially and temporally inhomogeneous inflow to the fan, in particular the tonal unsteady loading noise and the broadband turbulence ingestion noise, which depend mainly on the upstream installation conditions and are therefore called “inflow noise”. It is shown for a state-of-the art airto-water heat pump with 12 kW rated capacity and an evaporator heat exchanger in L-form that the inflow noise exceeds the self-noise of the fan given by the fan supplier. The conclusion is that the optimisation potential considering the inflow noise is more promising than considering a further self-noise optimisation of the fan. For the considered device, the inflow noise is analysed and characterized along with the causal inhomogeneous inflow conditions to the fan. Both numerical and experimental results are presented. Some optimizing approaches to reduce the inflow noise are investigated, considering both the fan design and installation arrangement. The A-rated total noise emission can be reduced, but, more important, the annoying tonal character of the noise can be attenuated significantly. |
||||||||||||||||||||